ILLUMINANCE LEVELS
- Category: Uncategorised
- Published: Tuesday, 22 March 2016 21:31
- Written by Rualight's IT Team
- Hits: 10645
* The provided illuminance levels comply to IEC (International Electrotechnical Commission) exactly.
Offices General offices………………………………………………….…500 Lux Open-plan offices…………………………………………………750 Lux Drawing offices…………………………………………………..1000 Lux Waiting rooms………………………………………………………200 Lux Computer work stations……………………………………....300 Lux
Shopping Centers Self-service shops and showrooms………………………500 Lux Shops (General)…………………………………………………...300 Lux Supermarkets……………………………………………………….750 Lux
Concert halls, cinemas and theaters General………………………………………………………………...100 Lux Foyer………………………………………………………….………...200 Lux
Museums and art galleries Exhibition - insensitive to light……………………………..300 Lux Exhibition - light-sensitive…………………………………….150 Lux
Education Classrooms…………………………………………….…………….500 Lux Lecture halls…………………………………………………………300 Lux Laboratories………………………………………………...........500 Lux Libraries……………………………………………………….………500 Lux |
Residences, hotels, restaurants Bedrooms (General)…………………………………………………………50 Lux Bed-head……………………………………………………………………….200 Lux Bathrooms (General)………………………………………………….....100 Lux Bathrooms (Shaving, make-up)………………………………………500 Lux Living rooms (General)……………………………………………….….100 Lux Living rooms ( Reading)…………………………………………….……500 Lux Stairs……………………………………………………………………………..100 Lux Kitchens (General)…………………………………………………………300 Lux Kitchens (Working areas)………………………………………….……500 Lux
Hospitals Night……………………………………………………………………………….50 Lux Daytime……………………………………………………………………..….200 Lux Treatment rooms…………………………………………………………..500 Lux Staff rooms………………………………………………………….………..100 Lux Laboratories…………………………………………………….…………….500 Lux
Industrial areas Textile workshops……………………………………………………..…..750 Lux Testing and inspection points……………………………………..…750 Lux Sewing workshops………………………………………...................750 Lux Leather workshops………………………………………………………..500 Lux Furniture workshops……………………………………….....…………500 Lux Processing of metal sheets…………………………………………….300 Lux |