* The provided illuminance levels comply to IEC (International Electrotechnical Commission) exactly.


 

Offices

General offices………………………………………………….…500 Lux

Open-plan offices…………………………………………………750 Lux

Drawing offices…………………………………………………..1000 Lux

Waiting rooms………………………………………………………200 Lux

Computer work stations……………………………………....300 Lux

 

Shopping Centers

Self-service shops and showrooms………………………500 Lux

Shops (General)…………………………………………………...300 Lux

Supermarkets……………………………………………………….750 Lux

 

Concert halls, cinemas and theaters

General………………………………………………………………...100 Lux

Foyer………………………………………………………….………...200 Lux

 

Museums and art galleries

Exhibition - insensitive to light……………………………..300 Lux

Exhibition - light-sensitive…………………………………….150 Lux

 

Education

Classrooms…………………………………………….…………….500 Lux

Lecture halls…………………………………………………………300 Lux

Laboratories………………………………………………...........500 Lux

Libraries……………………………………………………….………500 Lux

 

 

      Residences, hotels, restaurants

      Bedrooms (General)…………………………………………………………50 Lux

      Bed-head……………………………………………………………………….200 Lux

      Bathrooms (General)………………………………………………….....100 Lux

      Bathrooms (Shaving, make-up)………………………………………500 Lux

      Living rooms (General)……………………………………………….….100 Lux

      Living rooms ( Reading)…………………………………………….……500 Lux

      Stairs……………………………………………………………………………..100 Lux

      Kitchens (General)…………………………………………………………300 Lux

      Kitchens (Working areas)………………………………………….……500 Lux

 

      Hospitals

      Night……………………………………………………………………………….50 Lux

      Daytime……………………………………………………………………..….200 Lux

      Treatment rooms…………………………………………………………..500 Lux

      Staff rooms………………………………………………………….………..100 Lux

      Laboratories…………………………………………………….…………….500 Lux

 

      Industrial areas

      Textile workshops……………………………………………………..…..750 Lux

      Testing and inspection points……………………………………..…750 Lux

      Sewing workshops………………………………………...................750 Lux

      Leather workshops………………………………………………………..500 Lux

      Furniture workshops……………………………………….....…………500 Lux

      Processing of metal sheets…………………………………………….300 Lux